CONNECTIONS PLUMBING
All plumbing work must be carried out by a qualified person and in accordance with the Standard
AS/NZS 3500.4 and all local codes and regulatory authority requirements. In New Zealand the installation
must also conform with the New Zealand Building Code.
CONNECTION SIZES
Hot water connection: Rp 1¼.
Cold water connection: Rp 1¼.
Relief valve connection: Rp 3/4.
WATER INLET AND OUTLET
All pipe work must be cleared of foreign matter before
connection and purged before attempting to operate the water
heater. All olive compression fittings must use brass or copper
olives. Use thread sealing tape or approved thread sealant on
all fittings.
An isolation valve and non-return valve must be installed on the
cold water line to the water heater. An acceptable arrangement
is shown in the diagram or on page 26 for multiple installations.
Refer also to “Hot Water Delivery” on page 15.
A disconnection union must always be provided at the cold
water inlet and hot water outlet on the water heater to allow for
disconnection of the water heater.
This water heater has either a plastic dip tube or fitting liner in
the inlet and outlet fittings (see diagram). These must be in
place for the water heater to function properly. Do not remove or
damage them by using heat nearby. They will be pushed into
the correct position as the fitting is screwed in.
PIPE SIZES
The pipe sizing for hot water supply systems should be carried out by persons competent to do so, choosing
the most suitable pipe size for each individual application. Reference to the technical specifications of the
water heater and local regulatory authority requirements must be made.
TEMPERATURE PRESSURE RELIEF VALVE
The temperature pressure relief valve is shipped either under the top flap of the water heater carton or
behind the front cover or in a plastic bag attached to the water heater. The temperature pressure relief valve
must be fitted before the water heater is operated. Before fitting the relief valve, make sure the probe has not
been bent. Seal the thread with Teflon tape - never hemp. Make sure the tape does not hang over the end of
the thread.
Screw the valve into the correct opening (refer to the installation diagram on page 19) leaving the valve drain
pointing downwards. Do not use a wrench on the valve body - use the spanner flats provided. A copper drain
line must be fitted to the temperature pressure relief valve (refer to "Relief Valve Drain" on page 21).
The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the
insulation installed so as not to impede the operation of the valve. The insulation must be weatherproof and
UV resistant if exposed.
