GROSS SYSTEMS PERFORMANCE DATA—RQPM-A060
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 2280 1076] 1900 [897] 1520 [717] 2280 1076] 1900 [897] 1520 [717] 2280 1076] 1900 [897] 1520 [717]
DR
0 .04 .08 0 .04 .08 0 .04 .08
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
78.4 [23.0]
49.9 [14.6]
3.7
75.7 [22.2]
42.9 [12.6]
3.6
72.9 [21.4]
36.4 [10.7]
3.6
72.6 [21.3]
58.6 [17.2]
3.7
70.1 [20.5]
51.1 [15.0]
3.6
67.5 [19.8]
44.0 [12.9]
3.5
69.8 [20.5]
66.5 [19.5]
3.6
67.4 [19.8]
58.4 [17.1]
3.6
64.9 [19.0]
50.7 [14.9]
3.5
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
76.0 [22.3]
48.5 [14.2]
3.9
73.3 [21.5]
41.7 [12.2]
3.8
70.7 [20.7]
35.5 [10.4]
3.8
70.2 [20.6]
57.4 [16.8]
3.9
67.8 [19.9]
50.1 [14.7]
3.8
65.3 [19.1]
43.2 [12.7]
3.7
67.4 [19.8]
65.2 [19.1]
3.8
65.1 [19.1]
57.3 [16.8]
3.8
62.7 [18.4]
49.8 [14.6]
3.7
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
73.7 [21.6]
47.5 [13.9]
4.1
71.1 [20.8]
40.8 [12.0]
4.1
68.5 [20.1]
34.6 [10.2]
4.0
67.9 [19.9]
56.2 [16.5]
4.1
65.5 [19.2]
49.0 [14.4]
4.0
63.1 [18.5]
42.3 [12.4]
4.0
65.1 [19.1]
64.0 [18.8]
4.1
62.8 [18.4]
56.2 [16.5]
4.0
60.5 [17.7]
48.9 [14.3]
3.9
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
71.4 [20.9]
46.1 [13.5]
4.4
68.9 [20.2]
39.7 [11.6]
4.3
66.4 [19.5]
33.7 [9.9]
4.2
65.6 [19.2]
55.0 [16.1]
4.3
63.3 [18.6]
48.0 [14.1]
4.3
61.0 [17.9]
41.4 [12.1]
4.2
62.8 [18.4]
62.8 [18.4]
4.3
60.6 [17.8]
55.2 [16.2]
4.2
58.4 [17.1]
48.1 [14.1]
4.1
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
69.2 [20.3]
45.0 [13.2]
4.6
66.8 [19.6]
38.8 [11.4]
4.5
64.4 [18.9]
33.0 [9.7]
4.5
63.4 [18.6]
53.8 [15.8]
4.6
61.2 [17.9]
47.0 [13.8]
4.5
59.0 [17.3]
40.6 [11.9]
4.4
60.6 [17.8]
60.6 [17.8]
4.5
58.5 [17.1]
54.2 [15.9]
4.5
56.4 [16.5]
47.2 [13.8]
4.4
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
67.1 [19.7]
43.8 [12.8]
4.9
64.7 [19.0]
37.7 [11.1]
4.8
62.4 [18.3]
32.1 [9.4]
4.7
61.3 [18.0]
52.7 [15.5]
4.8
59.2 [17.3]
46.1 [13.5]
4.8
57.0 [16.7]
39.8 [11.7]
4.7
58.5 [17.1]
58.5 [17.2]
4.8
56.5 [16.6]
53.3 [15.6]
4.7
54.4 [15.9]
46.4 [13.6]
4.6
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
65.1 [19.1]
42.7 [12.5]
5.1
62.8 [18.4]
36.8 [10.8]
5.1
60.5 [17.7]
31.3 [9.2]
5.0
59.3 [17.4]
51.6 [15.1]
5.1
57.2 [16.8]
45.1 [13.2]
5.0
55.1 [16.1]
39.0 [11.4]
4.9
56.5 [16.6]
56.5 [16.6]
5.1
54.5 [16.0]
52.3 [15.3]
5.0
52.5 [15.4]
45.6 [13.4]
4.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
63.1 [18.5]
41.7 [12.2]
5.4
60.9 [17.8]
35.9 [10.5]
5.3
58.7 [17.2]
30.6 [9.0]
5.2
57.3 [16.8]
50.5 [14.8]
5.4
55.3 [16.2]
44.2 [13.0]
5.3
53.3 [15.6]
38.3 [11.2]
5.2
54.5 [16.0]
54.5 [16.0]
5.4
52.6 [15.4]
51.4 [15.1]
5.3
50.7 [14.9]
44.9 [13.2]
5.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
61.2 [17.9]
40.6 [11.9]
5.7
59.1 [17.3]
35.0 [10.3]
5.6
56.9 [16.7]
29.7 [8.7]
5.5
55.4 [16.2]
49.4 [14.5]
5.7
53.5 [15.7]
43.3 [12.7]
5.6
51.5 [15.1]
37.4 [11.0]
5.5
52.6 [15.4]
52.6 [15.4]
5.7
50.8 [14.9]
50.5 [14.8]
5.6
48.9 [14.3]
44.1 [12.9]
5.5
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].